DC:AC Ratio: Choosing an Inverter Size From Your Own Curve
In short This article turns inverter selection into an optimisation problem using your modelled DC output distribution, showing why UK conditions justify oversizing the array relative to the inverter and where that stops paying.
Most people pick an inverter by matching the number on the box to the number on the panels. A 4 kWp array gets a 4 kW inverter. It feels tidy, and it is usually the wrong answer for a UK roof.
The better approach is to treat inverter sizing as an optimisation problem. You have a modelled distribution of DC output across the year. You have a price list. You choose the AC rating that maximises the energy you actually keep per pound spent. This post walks through that with real numbers you can reproduce in a spreadsheet.
If you haven’t built your own demand profile yet, do that first via Sizing From Your Own Consumption Data. The inverter question is the second half of the same exercise.
Why nameplate matching wastes money
Panels are rated at Standard Test Conditions: 1000 W/m² irradiance, 25°C cell temperature. In the UK you almost never see 1000 W/m² on a tilted roof. Cloud, low sun angle, hot cells (which lose roughly 0.35% per °C above 25) and soiling all pull output down. Add cabling and mismatch losses and a typical array rarely delivers more than 75–80% of its kWp, even on its best day.
So a 4 kWp array on a 4 kW inverter leaves the inverter idle at the top of its range for nearly the whole year. You’ve paid for headroom that sunshine never fills.
The DC:AC ratio is simply array kWp divided by inverter AC rating. 4.0 kWp on a 3.0 kW inverter is 1.33. Installers in the UK routinely go to 1.3 or even 1.5. The question for you is where your own curve says to stop.
Build the DC output distribution
You need hourly (or half-hourly) modelled DC power for your specific roof. Free sources:
- PVGIS (the EU Joint Research Centre tool) gives hourly series for your postcode, tilt and azimuth. Download the CSV from the “Hourly data” tab.
- PVWatts-style models in Python via
pvlib, if you want to control losses yourself. - An AI assistant can write the pvlib script, or clean the PVGIS CSV, in a couple of minutes. Check its output against PVGIS totals before trusting it.
Take the PVGIS P column (W, for your chosen kWp and system loss, say 14%). Sort every hour’s output from highest to lowest. That is your duration curve.
Here is what a south-facing 4 kWp array at 35° in the Midlands typically looks like (illustrative figures, roughly 3,800 kWh/yr):
Output band (kW DC) Hours/yr Energy in band (kWh) Cumulative %
3.2 - 3.6 14 47 1.2%
2.8 - 3.2 58 174 5.8%
2.4 - 2.8 126 328 14.4%
2.0 - 2.4 210 462 26.6%
1.6 - 2.0 290 522 40.3%
below 1.6 1900 2267 100.0%
Output above 3.2 kW happens for about 14 hours a year. Above 2.8 kW, about 72 hours. The array hardly ever approaches its nameplate.
The clipping calculation
Clipping means the inverter caps AC output at its rating, and any DC above that is thrown away. With the table above, you can compute losses for each candidate inverter by summing energy above the cap.
For the 4 kWp array:
| Inverter | DC:AC | Energy clipped | % of annual yield |
|---|---|---|---|
| 4.0 kW | 1.00 | 0 kWh | 0% |
| 3.6 kW | 1.11 | about 3 kWh | 0.1% |
| 3.0 kW | 1.33 | about 40 kWh | 1.0% |
| 2.5 kW | 1.60 | about 190 kWh | 5.0% |
| 2.0 kW | 2.00 | about 560 kWh | 14.7% |
In a spreadsheet this is one formula per hour: =MAX(0, DC_kW - cap), summed. Do it for five caps and you have the table.
The curve is not linear. Dropping from 4.0 to 3.0 kW costs you 1% of yield. Dropping a further kilowatt costs you nearly fifteen times as much. That knee is the whole decision.
Put a price on it
Clipped energy has a value, but only the portion you would have used or exported at a worthwhile rate. Suppose:
- Self-consumption value: 25p/kWh (avoided import)
- Export: 15p/kWh under Smart Export Guarantee (Octopus Outgoing Fixed is in that region; check your own tariff)
- You self-consume about 40% of generation without a battery
Blended value is 0.4 × 25 + 0.6 × 15 = 19p/kWh. Clipped midday kWh in summer are mostly exported ones, so 15p is the fairer figure for the marginal loss.
Now the inverter price. Representative UK retail for a hybrid or string inverter, fitted-equivalent hardware cost: roughly £750 for 2.5 kW, £850 for 3.0 kW, £1,000 for 3.6 kW, £1,150 for 4.0 kW. Treat these as placeholders and use your actual quotes.
| Inverter | Hardware | Annual clip loss at 15p | 10-year clip loss | Hardware plus 10-year loss |
|---|---|---|---|---|
| 4.0 kW | £1,150 | £0 | £0 | £1,150 |
| 3.6 kW | £1,000 | £0.45 | £4 | £1,004 |
| 3.0 kW | £850 | £6 | £60 | £910 |
| 2.5 kW | £750 | £28 | £285 | £1,035 |
| 2.0 kW | £650 | £84 | £840 | £1,490 |
The minimum is the 3.0 kW unit at DC:AC 1.33. Go smaller and the lost energy outweighs the saving. Go bigger and you buy capacity that sits idle.
Note how shallow the bowl is between 3.0 and 3.6 kW: about £94 over ten years. Pricing noise in a real quote can swamp that, which is a useful finding in itself. Don’t agonise.
Why UK conditions justify going over 1.0
Three reasons, all visible in your curve:
- Latitude and cloud. At 52 to 56°N, peak irradiance on a tilted plane is modest, and diffuse light dominates for much of the year.
- Shoulder-season gain. An oversized array produces more in February, March and October, when the inverter is nowhere near its cap. Extra panels pay back in the months that matter, while clipping only bites in a handful of June afternoons.
- East-west roofs flatten the peak. Split a 4 kWp array across east and west faces and the peak DC drops to maybe 2.4 kW, while the daily curve broadens. An east-west array can run DC:AC of 1.5 or higher with clipping below 2%. Rerun your own PVGIS download for each orientation separately and add the two series before sorting.
Where oversizing stops paying
Three limits, and your model should test each.
Clipping itself. The table above shows it: past roughly 1.4 for a south roof, the losses accelerate.
Inverter input limits. Every inverter has a maximum DC input voltage and current per MPPT. A 3.0 kW unit might accept 4.5 kWp, but only if your string voltage at -10°C (cold panels raise voltage) stays below the ceiling. Manufacturer string-sizing tools (SMA Sunny Design, Fronius Solar.creator, Victron’s MPPT calculator) check this. Treat them as the hard constraint on your spreadsheet’s optimum.
Battery coupling. With a DC-coupled battery, “clipped” energy can charge the battery rather than vanish. That shifts the optimum toward more oversizing, since the loss is partly recovered. Model it: for each hour, send MAX(0, DC - cap) into the battery if there is headroom and SoC room. With a 5 kWh battery that fills most summer days by midday, the headroom is usually gone by the time clipping happens, so the recovered fraction is smaller than people expect. In the Midlands example, I’d count on recovering perhaps a quarter of the clipped kWh at 1.33, less at higher ratios.
There are also non-model limits. Check your DNO rules (G98 covers up to 3.68 kW per phase of inverter AC output; above that you need G99 approval). That cap is attached to the inverter’s AC rating, not the panels. It is one reason oversizing the array against a 3.6 kW inverter is so common in the UK: you stay in the simple notification regime while installing more DC. Also check the warranty: some manufacturers limit DC:AC to 1.3 to 1.5 and void cover beyond it.
A quick recipe
- Download hourly PVGIS data for your roof at your intended kWp.
- Compute clipped energy for caps from 70% down to 40% of kWp, in 10% steps.
- Multiply by your marginal £/kWh (export rate for midday, import rate if a battery or load absorbs it).
- Add real inverter quotes for each size.
- Pick the minimum of hardware plus ten-year loss, then check it against string limits and G98/G99.
On most south-facing UK roofs that lands between 1.2 and 1.4. On east-west roofs, 1.4 to 1.6. If your numbers disagree, trust the numbers: they came from your roof.